01 Selelekela

Ho ntsha metsi ka karolo e itseng (PD) ka har'a oli e qoelitsoeng Li-Transformer tsa Matla e ntse e le phephetso e tsebahalang lefatšeng ka bophara indastering ea transformer. Bahlahisi ba bangata ba bile le tahlehelo e kholo ka lebaka la ho hloleha ho amanang le PD.

Ho feta PD ho ka etsahala nakong ea liteko tsa fektheri, tlhahlobo ea motho oa boraro, kapa libakeng tsa bareki. Ho fumana mehloli ea PD hangata ho tšoana le "ho fumana nale ka har'a furu," e leng se lebisang ho sebetseng bocha matsatsi kapa likhoeli, ho baka tahlehelo e kholo ea boleng bakeng sa bahlahisi kapa basebelisi ba ho qetela.

Ka hona, ho hlahloba ka saense le ho tsebahatsa kapele lisosa tsa PD e feteletseng ke habohlokoa.

02 Tlhaloso le Tlhaho

Leha ho se na tlhaloso ya semmuso e teng, mongoli o hlalosa PD e le:
[Ho ntsha metsi ho etsahala libakeng tse fumanehang ka hare ho transformer e so kang ea baka ho senyeha ha insulation hang-hang kapa ho phatloha ha mocheso.]

Maemo a PD a fapana haholo empa a na le moelelo o tšoanang:
[Bofokodi ba sebopeho, thepa, kapa tlhahiso tsamaisong ea ho kenya mocheso bo baka ho sotha ha tšimo ea motlakase sebakeng seo ho feta matla a dielectric sebakeng seo, e leng se fellang ka ho senyeha ha ionization e pheta-phetoang, e nyane, e sa keneleng.]

Ka bokhutšoanyane, tlhaho ea PD e lutse ho tekanyo ea motlakase e sebakeng seo e fetang matla a tšimo ea PD ea ho qala.

03 Mabaka a Motheo

Ho latela mekhoa ea PD, ntho efe kapa efe e bakang masimo a motlakase a mangata sebakeng se itseng e ka baka ho feta ha PD.

3.1 Libaka tsa PD
PD e ka qala ho:

Lihlahla

 

Bafetoleli ba pompo ba OLTC/DETC

 

Baetapele

 

Mabili a moea

 

Likarolo tsa ho thella

 

Libaka tsa ho thibela ho ruruha/liphoso tsa ka hare

 

Oli ea transformer

Libaka tse kotsing ka ho fetisisa:Moea o foqoha ka har'a sehatsetsi se tiileng kapa lipululana tsa khase ka har'a oli.
Lebaka:Tlas'a khatello ea motlakase, matla a tšimo ea motlakase a lekana ka tsela e fapaneng le ea kamehla ea dielectric (ε).

Ho thibela pampiri ho ε ≈ 4.4

 

Likheo tsa moea ε ≈ 2.0
→ Phihlelo ea matla a tšimo a phahameng a ≈2.2 × moea o se nang letho.
Ka matla a tlase a ho senyeha (AC ≈2kV/mm), mathopa/dipululana di fetoha dintlha tse fokolang bakeng sa ho qalwa ha PD.

3.2 Mefuta ea PD
Mefuta e tloaelehileng ea PD ho Transformer e qoelitsoeng ka olis:

Ho ntšoa ha lipompong tsa khase

 

Ho tsoa ha metsi ho bakoang ke mongobo(sesebelisoa sa ho thibela mongobo)

 

Ho ntsha motlakase o bohale(malebela a motlakase o phahameng/oa fatše)

 

Ho ntsha metsi ho ka bang teng ka phaphametseng

 

Ho ntsha lekhalo la oli le bōpehileng joaloka wedge

 

Ho tsoa linthong tse nang le tšepe/litšila

 

Liphoso tse khomarelang(sekhomaretsi se feteletseng/sa boleng bo tlaase lipoleiting tsa ho khomarela/meheleng ea qetello)

Temohisiso ea Bohlokoa:

Ho feta ha PD ha ho amane le moralo hangata (monyetla oa ≈0.5%).
95%+ e bakoa ke liphoso tsa thepa, ts'ebetso, kapa tlhahiso.

Lebaka:Ha di-overvoltage (LI, LIC, SI, LTAC) di fetolwa ho ba motlakase o lekanang le wa motsotso o le mong o mamellang maqhubu a motlakase (Phetoho ea DIL), kaofela li feta motlakase oa tlhahlobo ea PD (IVPD). Sehatsetsi sa mantlha/sa longitudinal se etselitsoe boemo bo phahameng ka ho fetisisa ba motlakase.

Tjhe.

Mofuta oa PD

Sebaka

Mokhoa

Linyeoe tse Tloaelehileng

1

Ho ntsha Electrode e Bohale

Likarolo tse tlamang, tanka, bushing e ntseng e phahama, li-terminal tsa ho tlama ka loto

Radius e nyane e kobehileng → bongata ba tjhaja e phahameng → mahloriso a feteletseng a tšimo

Liboutu tse sa sireletsoang haufi le li-electrode tsa HV; mathoko a bohale holim'a tšireletso ea makenete

2

Phallo ea Khase/Ho Lahla ho se Nang Mohloli

Lipululana ka oli / likheo ka har'a insulation e tiileng

Phetoho e tlase ea dielectric (ε≈1) → khatello e phahameng ea tšimo + matla a tlase a ho senyeha (2kV/mm)

Sekheo se sa fellang; ho tlatsa oli ka potlako; sekhomaretsi se feteletseng/se fokolang masaleng a ho qetela/li-sphere tse lekanang

3

Ho Ntša ho Bakiloeng ke Mongobo

Mabili, ho kenya mocheso oa mantlha, li-lod

Mongobo o fokotsa matla a dielectric ka 60-70%

Ho omisa karolo e ka hare ea 'mele ho sa lekaneng; ho pepesehela moea o potolohileng haholo nakong ea kopano

4

Ho ka ’na ha Lahleha ho Phaphametseng

Boto ea khatiso, litšehetso tsa loto, li-shunt tsa makenete

Ho bokellana ha tjhaja → ho otla ha pelo ka tshohanyetso

Tšireletso ea makenete e sa koaheloang; masale a motlakase a sa hokahaneng hantle

5

Ho ntša metsi a litšila

Metsi/likhoele/likaroloana tsa tšepe ka oli

Ho sotha tšimo + metsi a eketsa khatello ea tšimo ka 2.9×

Ho sefa oli ho sa lekaneng; karolo e ka hare e silafetseng; ho kena ha mongobo

04 Pono

Ho utloisisa mefuta e tloaelehileng ea PD, mekhoa, libaka le lithuto tsa linyeoe ho bohlokoa bakeng sa ho rarolla mathata a reretsoeng.

Ha e kopantsoe le melao-motheo ea khokahano ea transformer, moralo oa sebopeho, litšobotsi tsa sebopeho sa maqhubu a PD, sebaka sa polarity, le liteko tsa tlhahlobo, tsebo ena e nolofalletsa ho tsebahatsa sesosa sa motso ka potlako le ho fokotsa tahlehelo ea boleng.