+86 18068001229 Litlhaloso tsa Tekheniki tsa ho Lemoha Phetoho ea Phetoho ea Motlakase o Phahameng
Litharollo tsa Transformer tsa JZP
- Selelekela
Ho feto-fetoha ha moea ho phahameng-Li-Transformer tsa Voltage ke taba ea bohlokoa ea polokeho, hangata e bakoang ke khatello ea mechine, potoloho ea mocheso, kapa litlamorao tsa potoloho e khuts'oane. JZP e le moetapele tlhahisong ea transformer, e latela Standard ea DL/T 1093-2018 bakeng sa Mokhoa oa Reactance ho Lemoheng ha ho Fetoha ha Phetoho ea Phetoho 'me e kopanya mahlale a tsoetseng pele ho netefatsa hore ho latela melao le ts'epo. Tokomane ena e hlalosa litlhaloso tsa tekheniki tsa JZP bakeng sa ho lemoha phetoho ea phetoho ea phetoho, e akaretsang mekhoa, litlhoko tsa lisebelisoa le mekhoa ea ts'ebetso.
- Sekhahla
Tlhaloso ena e sebetsa ho:
Mocheso o phahameng: 35 kV le ho feta.
Mefuta ea li-transformer: Mekhahlelo e meraro le e le 'ngoe Li-Transformer tsa Matla ka dibopeho tse kobehileng tsa ho phethoha tse tebileng.
Maemo a ho lemoha: Kamohelo ea fektheri, tlhahlobo ea kamora lipalangoang, le litekolo tsa liketsahalo tsa kamora potoloho e khuts'oane.
- Mekhoa ea ho Fumana Linotlolo
3.1 Mokhoa oa Karabelo (Ho Latela Melao ea DL/T 1093-2018)
Molao-motheo: E lekanya liphetoho karabelong ea ho potoloha (impedance) tlas'a motlakase oa AC ho lemoha ho sotha ha mechini.
Liparamente tsa bohlokoa:
Mekhahlelo ea maqhubu: 10 Hz - 1 MHz.
Ho nepahala: ± 0.5% bakeng sa boleng ba impedance.
Motlakase oa teko: ≤2 kV (AC).
Melemo: Ho ba le kutlo e phahameng ho diphetoho tse nyane (mohlala, ho kheloha ha impedance ya 0.1% ho bontsha mathata a ka bang teng).
3.2 Tlhahlobo ea Karabelo ea Makhetlo (FRA)
Mokhoa: E fiela maqhubu ho tloha ho 10 Hz ho isa ho 20 MHz ho hapa litšobotsi tsa resonance e potolohang.
Lintlafatso tsa JZP:
Ho nka disampole tsa qeto e phahameng: lintlha tse 50,000 tsa data bakeng sa tlhahlobo e nepahetseng ea sebopeho sa maqhubu.
Moralo o thibelang tšitiso: Ho itšehla thajana le ho sireletsa mahlo ho fokotsa lerata la motlakase.
Sephetho: Tlhahlobo ea papiso ea li-spectra tsa maqhubu a nalane khahlanong le a hona joale ho khetholla liphetoho litlhōrōng tsa resonance (mohlala, litemoso tse bakang phetoho ea >3 dB).
- Litlhoko tsa Tekheniki
- Mokhoa oa Teko
5.1 Litokisetso tsa Pele ho Teko
Tlhahlobo ea lisebelisoa: Netefatsa tekanyo ea sensor (mohlala, likhoele tsa Rogowski bakeng sa matšoao a maqhubu a phahameng).
Boemo ba transformer: Netefatsa hore transformer e felisitsoe matla ebile e tiile.
5.2 Ho Etsoa ha Teko
Tlhophiso ea lithapo:
Ho kobeha ha mantlha: Sebelisa lets'oao la teko (mohlala, motlakase o fetohang ho tloha ho buleheng ha sehatsetsi sa potoloho).
Ho kobeha ha bobeli: Hokela di-sensor ho lekanya matshwao a hlahisitsweng.
Litlhophiso tsa paramethara:
Mehato ea ho skena khafetsa: Kabo ea Logarithmic bakeng sa ho koahela ka botlalo.
Meeli ea ho qala: Itokise ka bohona ho latela bokhoni ba transformer (mohlala, li-transformer tsa 110 kV li hloka kutlo ea 100×).
Ho fumana lintlha:
Nka disampole tse fetang 200 ka ntlha e 'ngoe le e 'ngoe ea maqhubu.
Pontšo ea nako ea sebele ea boholo ba impedance/sekhutlo sa mohato.
5.3 Tlhahlobo ea Kamora Teko
Tlhahlobo e iketsang:
Bapisa le motheo oa fektheri (mohlala, ho kheloha ha impedance >2% ho bontša ho fetoha).
'Mapa oa 3D oa kabo ea khatello ea ho potoloha.
Ho Tlaleha: Hlahisa litlaleho tsa ho latela melao ka dikerafo le dikgothaletso tse ka sebediswang.
- Thuto ea Nyeoe: Transformer ea Polasi ea Moea
Boemo: Transformer ea polasi ea moea ea 33 kV e bontšitse ho kheloha ha impedance ea 15% kamora sefefo.
Tharollo ea JZP:
Ke entse teko ea FRA, e senola phetoho ea tlhoro ea resonance ea 4 kHz.
Ho khetholloa ho falla ha karolo e itseng ea ho kobeha ka setšoantšo sa mocheso sa 3D.
Ho kgothalletsa ho kgutlisa morao, ho thibela ho hloleha ho ka bang kotsi.
- Ho latela Melao le Setifikeiti
Maemo a machaba: IEC 60076-18, IEEE C57.152.
Litifikeiti: CE, UL, ISO 9001.
Netefatso ea mokha oa boraro: Litlhahlobo tsa selemo le selemo tsa TÜV Rheinland.
- Qetello
Sistimi ea ho lemoha phetoho ea sebopeho sa JZP e kopanya tekanyo e nepahetseng, tlhahlobo e tsamaisoang ke AI, le ho latela ka botlalo DL/T 1093-2018. Ka ho kopanya mahlale a morao-rao joalo ka FRA e sebelisoang khafetsa le tlaleho e iketsang, re netefatsa hore li-transformer li sebetsa ka mokhoa o sireletsehileng le ka katleho mererong ea lefats'e.